Air Release Valve

Double Orifice Air Release Valve

Double orifice air release valve for bulk air discharge, vacuum admission and automatic air release under pressure.

Double Orifice Air Release Valve

 Double Orifice Air Release Valve Manufacturer in Italy

Double Orifice Air Release Valves combine two air passages to manage air movement in water transmission and distribution pipelines. The large orifice discharges air during pipeline filling and admits air during draining, while the small orifice releases accumulated air during pressurised operation. This arrangement helps reduce air pockets, maintain flow efficiency and limit excessive vacuum conditions.

Double orifice air release valve selection depends on orifice capacity, operating pressure, float construction and sealing materials. Pipeline filling and draining rates, elevation profile and required air discharge and admission capacity must also be evaluated to determine a suitable valve configuration.

Large and Small Orifice Operation

The large orifice allows displaced air to escape as water enters the pipeline. When the water level reaches the valve chamber, the float mechanism closes the main air passage.

During pipeline draining or negative-pressure conditions, the large opening admits air to help limit vacuum formation.

The small orifice operates during normal pressurised service, releasing accumulated air without interrupting pipeline operation.

Float Mechanism and Sealing Construction

The valve operates automatically through float movement and changes in water level within the chamber.

Depending on the design, separate floats or an integrated mechanism control the two air passages. The sealing arrangement must provide reliable closure under positive pressure while allowing air discharge or admission when required.

Ductile iron bodies, stainless steel internal components and suitable elastomeric seals may be selected according to operating pressure, water quality and corrosion requirements.

Air-Flow Capacity and Pipeline Installation

Valve sizing depends on filling and draining rates, operating pressure, elevation profile and permissible differential pressure.

Large-orifice discharge and admission capacities should be assessed using manufacturer performance curves. The small-orifice capacity must also be suitable for releasing accumulated air at normal pipeline pressure.

Installation locations are typically identified through hydraulic analysis, particularly at pipeline high points where air can accumulate.

Where rapid air expulsion could cause pressure transients, controlled-closing or anti-slam features may be required.

FAQ

Frequently Asked Questions

Find quick answers to common questions about this product.

A double orifice air release valve combines large-volume air discharge and admission with automatic release of accumulated air under pressure. A conventional single-orifice automatic air release valve primarily removes trapped air during pressurised operation. The appropriate choice depends on the air-management requirements of the pipeline.